9 Creating SNVTs TAC Xenta Server – Gateway, Technical Manual
76 (184) Schneider Electric Buildings AB, June 2011
04-00124-06-en
9.1.2 Connecting a Signal to an Output SNVT
An output SNVT created in the Xenta 913 is given its value by using a
connection object. For more information about connection objects, see
Section 10.2, “Connection Objects”, on page 87.
To connect a signal to an output SNVT
1 In the system pane, in the example, expand ACME_Gateway-
Engineering-Connection_Objects.
2 Right-click Connection_Objects, point to New, and then click
Folder.
3 Type the name. In the example “SNVTs”.
4 Right-click SNVTs, point to New, point to Object, and then click
Connection Object.
5 Type the name. In the example, “Tot_real_power”.
6 Expand the connection object.
7 In the system pane, from ACME_Gateway-Engineering-
PM710_Signals, drag Tot_real_power to the From signal in the
Tot_real_power connection object.
8 In the network pane, from IP Backbone-TAC_Xenta_913-SNVTs-
LonMarkObjects-Energy_Meter-NetworkVariables, drag
nvo_Tot_real_pow to the To signal in the Tot_real_power connec-
tion object.
9 In the system pane, click the Tot_real_power connection object.
10 In the properties pane, in the Send Option list, click Write on
change.
11 Generate and send the project to the Xenta 913.