Product manual
8 Connecting to the LonWorks Network TAC Xenta Server – Gateway, Technical Manual
70 (184) Schneider Electric Buildings AB, June 2011
04-00124-06-en
Before you close the connection manager, verify the connections to
ensure that the connections are valid.
7 In the Connection Manager dialog box, click Validate.
8 Click OK.
9 In the system pane, right-click the new multi-connection object. In
the example, 1.
10 Click Rename.
11 Type the name. In the example, “PM710_to_RTU4”, and then
press ENTER.
Your project should now appear as follows:
12 Generate the project and send it to the Xenta 913.
The gateway application is now in place in the Xenta 913.
For more information about working with the connection manager, see
Section 10.3, “Multi-Connection Objects”, on page 88.