Product manual
TAC Xenta Server – Gateway, Technical Manual 8 Connecting to the LonWorks Network
Schneider Electric Buildings AB, June 2011 69 (184)
04-00124-06-en
4 In XBuilder, in the system pane, drag the receiving signal to the To
column in the connection manager. In the example,
ACME_Gateway-Engineering-RTU4_Signals-
Usage_Inst_curr_ph_1 to the first row of the To column in the
connection manager.
5 In the connection manager, in the Send Option list, click Write
initially and on change.
6 In the example, connect the signals using the procedure above for
the following signals in ACME_Gateway-Engineering-
PM710_Signals and ACME_Gateway-Engineering-
RTU4_Signals.
The connection manager should now appear as follows:
Table 8.2: Signals transferred from PM710 to RTU4.
PM710_Signals RTU4_Signals Send Option
Inst_current_phase_1 Usage_Inst_curr_ph_1 Write initially and on change
Voltage_ph1_to_N Usage_Volt_ph1_to_N Write initially and on change
Frequency Usage_Frequency Write initially and on change
Tot_real_power Usage_Tot_real_power Write initially and on change
Prim_current_tr Usage_Prim_curr_tr Write initially and on change
Sec_current_tr Usage_Sec_curr_tr Write initially and on change
Tip
• If you do not select anything in the Send Option list or do not
type a a value in the Period (s) box, the connection is automati-
cally set to Periodically and 10 s.