TAC Xenta Server – Gateway, Technical Manual 7 Adding the TAC Xenta 913 to the LonWorks Network
Schneider Electric Buildings AB, June 2011 57 (184)
04-00124-06-en
14 On the Xenta 913, press the service pin button.
15 Under Load XIF file from, use the .xif file created in your
XBuilder project or leave the box empty.
16 Click Finish and close the wizard.
17 In the folders pane, right-click the LonWorks device. In the exam-
ple, VistaSRV1-LTA_1-ACME_Inc-2nd_Floor_LW-
ACME_Gateway.
18 Click Commission and Download.
19 Click OK.
20 In the TAC Vista Load dialog box, click Commission and
Download .
21 Click Continue.
22 When the operation is completed, click Close.
23 In the folders pane, click Refresh and verify that the Xenta 913 is
online.
The Xenta 913 is now added to the LonWorks network and signals from
the Modbus device can now be set up to be transferred to, for example,
the RTU4 device.
Note
• If the Xenta 913 has yet to be installed on the LonWorks net-
work, the Neuron ID for the Xenta 913 can be typed in.
Note
• By selecting the device type X511/527/913 the Xenta 913 auto-
matically becomes a member of the TAC group. In this case
Vista allows the Xenta 913 to be installed without defining the
.xif file.