Product manual
6 Visualizing Signals TAC Xenta Server – Gateway, Technical Manual
54 (184) Schneider Electric Buildings AB, June 2011
04-00124-06-en
6.4 Verifying the Modbus Communication
After the project is sent to the Xenta 913, the communication on the
Modbus network can be verified. Open the web pages containing the
signals from the energy meter and verify that they appear as expected.
In the Xenta 913, the web site appears as follows.
6.5 Monitoring the Communication
By logging into the Xenta 913 web site, the communication status can
be monitored on the Communications page. The data from the energy
meter can be inspected on the PM710_Values page.
However, if the pages do not update or appear incorrect a diagnostic log
in the Xenta 913 can be inspected. For more information about monitor-
ing communication, see Chapter 12, “Working with Third-party Com-
munication Diagnostics”, on page 99.
Important
• To verify communication, generate the project and send it to the
Xenta 913.