Product manual
B Protocols TAC Xenta Server – Gateway, Technical Manual
174 (184) Schneider Electric Buildings AB, June 2011
04-00124-06-en
B.8 Clipsal C-Bus Lighting Control
The Xenta 913 can be configured to connect to a Clipsal C-Bus serial
adaptor to allow monitoring and control of a lighting system through an
I/NET or LON control system.
A number of C-Bus Group Variables can be connected to a correspond-
ing set of LON Network Variables or I/Net Points to allow C-Bus light-
ing groups to be monitored and/or controlled. These Group Variables
may be distributed amongst one or more C-Bus applications as applica-
ble.
Fig. B.8: Clipsal C-Bus lighting control
Value exchange
C-Bus Network
RTU or ASCII
RS-232 A
Clipsal C-Bus
PC Interface
Clipsal C-Bus
LON or I/NET Control System
Xenta 913