Product manual

TAC Xenta Server – Gateway, Technical Manual B Protocols
Schneider Electric Buildings AB, June 2011 173 (184)
04-00124-06-en
Signal DataType – Is set to a default of INTEGER or REAL
based on the selected field type. But the default data type may sub-
sequently need to be changed to suit the applied conversion coeffi-
cient. For example, if a gain of 0.1 is applied to an integer it will
produce a real value, so the default DataType would be changed
to REAL in this case.
Signal Measurement System – The measurement system param-
eters are normally set to match the units shown in the [] brackets
of the selected field type. But the standard units may need to be
changed to suit the applied conversion coefficient. For example, if
a gain of 0.001 is applied to convert from kWh to Wh then a prefix
of k would need to be selected for the measurement system units.