Product manual
TAC Xenta Server – Gateway, Technical Manual B Protocols
Schneider Electric Buildings AB, June 2011 135 (184)
04-00124-06-en
• Coefficient Gain and Offset – Allow the raw register value to be
converted into the desired absolute units. If the raw register value
is a real number then normally no conversion is necessary and the
default gain and offset of 1 and 0 can be used. But if the raw regis-
ter value is an integer then it often needs to have a gain and offset
applied.
As an example, to pass a control system value representing voltage
to the master through an unsigned integer register requires the
actual voltage to be multiplied by 10 if 1 digit of resolution is
required. In this case the Xenta 913’s gain should be set to 0.1 to
convert the raw units (10*V) into the required absolute units (V).
• Signal DataType – Is set to a default of BOOL, INTEGER or
REAL based on the selected register type. But the default data
type may subsequently need to be changed to suit the applied con-
version coefficient. For example, if a gain of 0.1 is applied to an
integer it will produce a real value, so the default DataType would
be changed to REAL in this case.
• Signal Measurement System – The measurement system param-
eters need to be manually set to match the absolute form of the
register value after conversion by the coefficient gain and offset,
being either an enumeration or analogue engineering unit as appli-
cable.