Product manual
B Protocols TAC Xenta Server – Gateway, Technical Manual
126 (184) Schneider Electric Buildings AB, June 2011
04-00124-06-en
integer it will produce a real value, so the default DataType would
be changed to REAL in this case.
• Signal Measurement System – The measurement system param-
eters need to be manually set to match the absolute form of the
register value after conversion by the coefficient gain and offset,
being either an enumeration or analogue engineering unit as appli-
cable..
Note
• For the Modbus Master protocol, communications are improved
if the signals (register addresses) are added in sequence in the
device editor starting with the lowest register number.