Product manual

1 About this Manual TAC Xenta Server – Gateway, Technical Manual
12 (184) Schneider Electric Buildings AB, June 2011
04-00124-06-en
Table 1.1: Major features
Product LON I/NET MicroNet ModBus Web
a
I/O
Modules
Xenta
Supp.
b
Xenta 511 x x C x
Xenta 527 x x x C x
Xenta 527-NPR x S
Xenta 555 x x x C x
Xenta 701 x x ST 10
Xenta 711 x x C 10 x
Xenta 721 x x ST 20 x
Xenta 731 x x x x C 20 x
Xenta 913
c
xx x S
a. S – Service. Means that the web interface is automatically generated in XBuilder and only contains values
in value pages and is aimed for commissioning and service. It is not possible to have any end-user web
content, such as graphics, trend viewers, alarm viewers or value pages.
T – Time Object Pages. Means that Time Object Pages can be added to the XBuilder project. These will
only appear for Xenta Servers 701/721 in TAC Vista Workstation and can be used to control Xenta Server
time charts from Vista Workstation
C – Custom. Means that the web interface is totally configurable in XBuilder; navigation and all features
for creating a full end-user web are available.
b. Xenta Supp. – Xenta 280/300/401 support. Means that Xenta 280/300/401 can be installed on the Lon-
Works network beneath a Xenta 700 and are fully supported by both the Xenta 700 and TAC Vista on top
of Xenta 700.
c. The Xenta 913 also supports BacNet, M-Bus, and C-Bus.