Product manual

TAC Xenta Server – Gateway, Technical Manual 12 Working with Third-party Communication Diagnostics
Schneider Electric Buildings AB, June 2011 103 (184)
04-00124-06-en
At a verbosity level of 9, the log records all communications activity
between the Xenta 913 and the target system. However, the large vol-
ume of messages resulting may obscure simple configuration problems,
so this is normally only used in short bursts to locate protocol faults.
Verbosity is set using the following command format:
vx V n
where V selects the verbosity command, and n is the required verbosity
level (0 to 9). Simply typing vx v reports the current verbosity level.
Output log file
The log file is printed using the following command format:
vx O
Simply typing vx O (letter O) prints the log file on the screen.