Specifications
2009
2010
76
FURTHER INFORMATION
RJ45 SOCKETS
RJ45 PLUG
The untwisted length of a section of cable as the result of a termination to-
wards a connecting component must be as short as possible. Only the absolute-
ly necessary amount of wire must be unwound for terminating and finishing
the cable. Furthermore, for connections with category 5 components and above,
the detwisting of the cable must not exceed a length of 13 mm.
The two crimping methods are equivalent, but cannot coexist in a single in-
stallation. It follows that once the type of connection (A or B) has been cho-
sen for a cabling system, it cannot be changed.
The 100 Ω patch cord cable (flexible conductor), must be connected at both
ends with a modular male connector (plug), of the 8 position RJ45 type.
•
Follow the instructions regarding connection to the RJ45 jack.
When making up patch cords, we recommend following some simple pre-
cautions to optimise the operation of the system
• after crimping, check that the
cable is round in cross-section
within 6 mm of the connector.
• When using self-crimping sys-
tems, check that the insulation
has been properly perforated.
• In the case of screened cables,
the cable screen must be secure-
ly attached to the plug with the
specially provided collar.
For further information, request the FANTO
Net
technical manual.