Technical information
F-26266-7 © 2010 Schneider Electric. All rights reserved.. 7
Figure-4 MN 200 Terminal Connections.
Applications which use a 10K Thermistor Sensor (non-850 series) universal input require
an 11K ohm shunt resistor kit, AD-8969-206. Install resistor across universal input and common.
Applications which use 0 to 20 mA analog inputs require a 250 ohm shunt resistor kit, AD-8969-202.
Install resistor across universal input and common.
24H
24G
GND
C1
NO1
C2
NO2
C3
NO3
C4
NO4
C5
NO5
C6
NO6
Ul1
COM
UI2
COM
UI3
AO2
COM
AO1
DI2
COM
DI1
S-LK
S-LK
LON
LON
Universal Inputs
0 to 5 Vdc
0 to 20mA
10K Thermistor
1K Balco
1K Platinum
Digital
Analog Outputs
0 to 20mA into an
80 to 550Ω load
Sensor Link
Supports
1 TAC I/A Series MN-Sx
Sensor
Service Pin Button
AC Power
24 Vac, 50/60 Hz
Class 2 (EN 60742)
15 VA per Controller
plus DO load if
same transformer is
used.
Digital Outputs
24 Vac, Class 2,
or 24 Vdc (or less)
24 VA per output
Pilot Duty
Form A (SPST)
Normally Open (NO)
Digital Inputs
Dry Contact
2
To detect a closed switch, maximum resistance must be less than 300 ohms .
To detect an open switch, minimum resistance must be greater than 1.5K ohms.
1
4
1
2
3
4
1
To detect an open switch, minimum resistance must be greater than 100K ohms.
3
5
.Input signals of 1 to 11 Vdc must be converted to 0.45 to 5 Vdc with a voltage divider, AD-8961-220.
5
65
.
65
L
ONWORKS Network Jack
LONWORKS Network
Communications
FT 3150 Transceiver