Figure-3 MN 150 Terminal Connections.
Applications which use a 10K Thermistor Sensor (non-850 series) universal input require
an 11K ohm shunt resistor kit, AD-8969-206. Install resistor across universal input and common.
Applications which use 0 to 20 mA analog inputs require a 250 ohm shunt resistor kit, AD-8969-202.
Install resistor across universal input and common.
24H
24G
GND
C1
NO1
C2
NO2
Ul1
COM
UI2
COM
UI3
AO2
COM
AO1
S-LK
S-LK
LON
LON
Universal Inputs
0 to 5 Vdc
0 to 20mA
10K Thermistor
1K Balco
1K Platinum
Digital
Analog Outputs
0 to 20mA into an
80 to 550Ω load
Sensor Link
Supports
1 TAC I/A Series MN-Sx
Sensor
Service Pin Button
AC Power
24 Vac, 50/60 Hz
Class 2 (EN 60742)
15 VA per Controller
plus DO load if
same transformer is
used.
Digital Outputs
24 Vac, Class 2,
or 24 Vdc (or less)
24 VA per output
Pilot Duty
Form A (SPST)
Normally Open (NO)
2
To detect a closed switch, maximum resistance must be less than 300 ohms .
To detect an open switch, minimum resistance must be greater than 1.5K ohms.
1
2
3
4
1
To detect an open switch, minimum resistance must be greater than 100K ohms.
3
5
.Input signals of 1 to 11 Vdc must be converted to 0.45 to 5 Vdc with a voltage divider, AD-8961-220.