Technical information

2 © 2010 Schneider Electric. All rights reserved. F-26266-7
Applicable Documentation
Installation
Inspection Inspect carton for damage. If damaged, notify carrier immediately. Inspect controllers for
damage upon receipt.
Requirements
(These items not provided)
Installer must be a qualified, experienced technician.
Job wiring diagrams
To ol s :
Drill and bits for panel mounting screws
Digital Volt-ohm meter (DVM)
Static protection wrist strap
MNA-FLO-1 enclosure for connecting to conduit (optional)
Class 2 power transformer supplying a nominal 24 Vac (20.4 to 30 Vac) with a minimum
rating of 15 Va, 50/60 Hz per controller plus Digital Output (DO) loads (if same
transformer is used). In European Community, transformer must conform to EN 60742
Terminators:
One LON-TERM1 terminator required for each free topology segment
Two LON-TERM2 terminators required for each bus topology segment
Two #6 pan head panel mounting screws or 35mm DIN rail for mounting
F-Number Description Audience Purpose
F-26277
TAC I/A Series MicroNet
MN-Sx Series Sensors
General Instructions
Application Engineers
Installers
Service Personnel
Start-up Technicians
Provides step-by-step installation and checkout procedures for TAC
I/A Series MicroNet MN-Sx Series Sensors. Also contains
instructions for sensor operation.
F-26303
TAC I/A Series MicroNet
System Overview
Application engineers
Installers
Start-up technicians
Service personnel
Provides an overview of the TAC I/A Series MicroNet System. It
includes brief descriptions of the hardware and software components,
and how they may be combined to create MicroNet networks and
stand-alone systems.
F-27254
WorkPlace Tech Tool 4.0
Engineering Guide
Application Engineers
Installers
Service Personnel
Start-up Technicians
Provides engineering and technical information for applying and
using all aspects of WorkPlace Tech Tool.
F-26507
TAC I/A Series MicroNet
Systems Engineering
Guide
Application Engineers
Installers
Service Personnel
Start-up Technicians
Provides engineering and technical information to assist in
designing a complete MicroNet controller system using different
architectures, components, and software.
F-27255
WorkPlace Tech Tool 4.0
User’s Guide
Application Engineers
Installers
Service Personnel
Start-up Technicians
Provides step-by-step instructions for using WorkPlace Tech Tool.
F-26363
EN-206 Guidelines for
Powering Multiple Full-
Wave and Half-Wave
Rectifier Devices from a
Common Transformer
Application Engineers
Installers
Service Personnel
Offers guidelines for avoiding equipment damage associated with
improperly wiring devices of varying rectifier types. Contains
instructions for identifying device rectifier type, guidelines for
correctly powering devices of varying rectifier types, and examples
illustrating proper power wiring techniques.