Power Supply Wiring
Caution:
MicroNet I/A Series Controllers are Class 2 only devices and must be connected to a
Class 2 source. Class 2 circuits must not intermix with Class 1 circuits.
This product contains a non-isolated half-wave rectifier power supply and must not be
powered by transformers used to power other devices containing non-isolated full-wave
rectifier power supplies. Refer to EN-206, Guidelines for Powering Multiple Devices
from a Common Transformer, F-26363, for detailed information.
Power wiring cannot be intermixed with LON, S-Link, UI, AO, or DI wiring.
Use a Class 2 power transformer supplying a nominal 24 Vac (20.4 to 30 Vac) with a
minimum rating of 15 VA at 50/60 Hz plus digital output loads (144VA using 6 DOs or
96VA using 4 DOs if same transformer is used). The supply to the transformer must be
provided with a breaker or disconnect. In European Community, transformer must
conform to EN 60742.
The Class 2 power transformer may be used to power multiple Class 2 powered devices
provided that the transformer is properly sized to power all equipment simultaneously
and all devices contain the same type of rectifier power supplies or internal isolation.
The transformer frame must be grounded.
When powering multiple Class 2 devices from the same Class 2 power transformer,
polarity must be observed (24H connected to 24H and 24G connected to 24G).
Note:
Power wiring terminals accept one 16 gage (1.29mm) or two 18 gage (1.02mm) wires.
Power wiring can be intermixed with DO wiring.
Twisted or untwisted cable can be used for power wiring.
To preserve the integrity of the network, the LON wiring connecting a TAC I/A Series
MicroNet controller to an MN-Sx sensor must be run to the sensor and back, in daisy-
chain fashion. A wire “spur” must not be used to connect the sensor to the controller.
Figure-8 and Figure-9 are acceptable wiring configurations.
Figure-8 Single Controller Powered from a Separate Class 2 Power Source.
Ground Frame
of Transformer
to Known Ground
Primary 24 Vac
Secondary
Class 2
MNL-10Rxx
MNL-15Rxx
MNL-20Rxx
MN-Sx
Sensor
S-Link
1
Optional connection
provides local access
to the L
ONWORKS network.
1
To rest of the LONWORKS
network.
LON
Observe Free or Daisy chain topology when making connection to rest of network.