Technical information
F-26266-7 © 2010 Schneider Electric. All rights reserved.. 11
Digital Outputs (DO)
Caution:
• DO terminals accept one 16 gage (1.29mm) wire or two 18 gage (1.02mm) wires. The
selected wire gage must be consistent with the load current rating.
• DO wiring cannot be intermixed with DI, UI, S-Link, LON and AO wiring.
• MN 100, MN 150, and MN 200 controllers are Class 2 devices. Each digital output can
support up to 24 Vac/Vdc at 1.0 amp (24 VA) pilot duty.
Note: Digital Output wiring can be intermixed with class 2 power wiring.
Each DO is an isolated Form A (SPST) relay. If the transformer is sized correctly, the 24 Vac
Class 2 Controller power source (Figure-7) may be used for load power.
Table-2 Relay Output Load Specifications.
Figure-7 DO Loads and Controller Power Sharing Common Transformer.
Specification Value
Maximum Relay Contact Switched Output Voltage
voltage at 24H
terminal
a
Maximum Output Load @ 24 VAC, Pilot Duty 24 VA
Minimum Permissible Load 10.0 mA at 5Vdc
Maximum Off-state Leakage Current 3.5 mA
Minimum Cycles at Rated Load @ 0.4 Power Factor 300,000 cycles
a
Switched output voltage is equivalent to value of input voltage.
24 H
24 G
Class 2
Transformer
24 VacPrimary
GND
Load
Load
Load
NO1
NO2
NOx
C1
C2
Cx