Specifications
D)  Controller Lights (LEDs) 
The controller is equipped with 3 LEDs that are green (closest to edge of controller), yellow, and red 
(closest to center of controller). 
(1) Green - Power and Data Transmission LED. If this light is off, check controller power. Under 
operation conditions, this light should flicker or be ON. This light will flicker when data is being 
transmitted onto the communications network. 
(2) Yellow - Data Reception LED. This light will flicker when data is being received from the 
communications network. 
(3) Red - Service LED. This light will flicker when a controller is being programmed over the network. 
If the light steadily blinks at the rate of once per second, the controller is not programmed. Contact 
the factory for a replacement controller. 
If this light remains ON, the controller has detected an internal error and requires service. Remove 
controller power for 15 seconds, and then restore power. If the LED remains ON, check the 
controller power supply (nominal 24 VAC across terminals 24H and 24G). If the LED remains ON, 
turn off the unit and replace the controller. 
4) Standard Inputs 
The following inputs are the digital (binary) inputs used with the controller. Some items are optional and 
others are used only with specific control packages. Please see Section 6 for details on the unit sequence of 
operation. 
A)  Water Coil Low Limit 
This input is attached to the coil used on all units with steam or water. A low limit switch is connected in 
parallel with the outdoor air temperature sensor (OAT). When the low limit switch closes, it short circuits 
the OAT sensor input, thus initiating low limit mode. 
B) Occupancy Input 
If the unit is connected to a LON network and the network occupancy input is bound to an occupancy 
controller, the network initiates occupied/unoccupied modes, regardless of the status of the physical 
occupancy input. Without a network, all units use controller digital input 1 (DI1, terminal #26) for the 
occupancy status input. When terminal DI1 is connected (input switch closed) to a common terminal 
(COM, #22), the controller switches to unoccupied mode, unless the unoccupied override button on the 
dual-mount thermostat is pressed. When terminal DI1 is disconnected from COM, the unit enters 
occupied mode. 
This input may be factory connected to an optional day/night relay, where the relay coil must be field 
wired to an occupancy controller. This relay is factory wired so that the relay is energized for unoccupied 
mode and de-energized for occupied mode. When ordered, this relay is mounted on the control panel. 
This input may be factory connected to an optional 7-day timeclock. This timeclock has an override 
switch (holiday switch) built into the clock face that can be used to force the unit into occupied or 
unoccupied modes. When ordered, this timeclock is mounted on the control panel. 
C) Change-over Input 
This input is used only on 2-pipe, systems with chilled water. A changeover switch (aquastat) is 
connected between controller terminals DI2 (#24) and COM (#25). The switch contacts close when the 
switch senses that the water temperature is below 65°F, thus indicating that chilled water is available 
and initiating cooling mode. The unit enters heating mode when the contacts open at 85°F. 
D)  Refrigerant Low Limit 
This input is used with DX coils on self-contained unit ventilators. A low limit switch is connected 
between controller terminals DI2 (#24) and COM (#25). The switch contacts close when the DX coil 
temperature falls below 28°F, thus prompting the controller to disable the compressor. 
5) Standard Outputs 
Some output items are optional and others are used only with specific control packages. Please see Section 
6 for details on the unit sequence of operation. 
A)  Outdoor Air / Return Air Damper Actuator 
This actuator is connected to 24 VAC power and is controlled with a 4-20 mA signal from Analog Output 
1 (AO1, #23). The actuator will close the outdoor air damper on a power failure. A 4 mA signal drives 
the damper fully closed, while a 20 mA signal drives the actuator to full open position. 
7/1/03  Part Number 011-200001-003 Page 7 










