Specifications
1)  Dual-Mount Thermostat (Wall Thermostat) 
A) Use 
The dual-mount thermostat or "wall 'stat" is factory mounted in the unit for setpoint adjustment and 
diagnostics. As factory wired, this thermostat is NOT used to sense temperature. This thermostat may 
be removed from the unit and remotely mounted. In the remote location, the thermostat may be used 
for setpoint adjustment and diagnostics, but it can also be used to sense the space temperature. See 
Section 1-E for mounting details and instructions on using this thermostat to sense space temperature. 
B)  Keypad Layout and Display Icons 
Figure 1 - Buttons & Icons 
AUTO
73.9
°F
°C
%
Fan Button
Setpoint Button
Mode Button
LCD Display
Override Button
Override LED
Up/Down Button
Cool
Fan
Heat
Off
On
Outdoor Air
%
Relative Humidity
Unoccupied
C) Adjusting Setpoints 
The Mode Button and Fan Button are not used. 
The setpoint button is used in conjunction with the up/down button to set one of four setpoints. Press 
the setpoint button once to get the first setpoint, twice for the second setpoint, etc. Use the up/down 
button to increase/decrease the setpoint value. The setpoints are: 
Setpoint # Point  Range  Default Icons Displayed 
1  Space Setpoint  65 - 85 °F  74 °F  °F 
2  Unoccupied Offset  0 - 15 °F  5 °F  °F, Unoccupied 
3  Minimum Position  0 - 100 %  10 %  %, Cool 
4  Deadband  1.5-3 °F  2 °F  °F 
(1) Space Setpoint - Used to calculate the heating and cooling setpoints. 
(2)  Unoccupied Offset - Used to calculate the unoccupied heating and cooling setpoints. This value is 
added to the cooling setpoint and subtracted from the heating setpoint. 
(3) Minimum Position - sets the minimum position of the outdoor air damper in terms of damper 
actuator position. Value is used only in occupied mode. 
(4) Deadband - offset value used calculate the heating and cooling setpoints. 
Occupancy Offset = 0°F in occupied mode and Unoccupied Offset in unoccupied mode. 
Heating setpoint = Space Setpoint - Deadband - Occupancy Offset. Cooling setpoint = Space Setpoint + 
Deadband + Occupancy Offset. 
D) Unoccupied Override 
A single press of the override button is used to provide a 2 hour unoccupied override. The override LED 
is lit during override. The occupancy override may be canceled by pressing the override button for more 
than 4 seconds, but less than 8 seconds. 
7/1/03  Part Number 011-200001-003 Page 2 