Specifications
J)  Damper Controlled Chilled Water Cooling with Electric Heat 
Fan Operation 
The supply fan shall run continuously in the occupied and tenant (unoccupied) override modes. The fan shall 
cycle with calls for cooling or heating in the unoccupied mode. 
Cooling Operation 
When the space temperature exceeds the cooling setpoint, a proportional-integral control loop shall position 
the face & bypass damper to maintain the space temperature. When the space temperature falls below the 
cooling setpoint, the face & bypass damper shall close (bypass). 
The face and bypass damper shall be driven closed (full bypass) if the discharge air temperature falls below 
55°F OR the low limit thermostat closes. The damper shall remain closed until the discharge air temperature 
exceeds 57°F AND the low limit thermostat opens. 
Heating Operation 
There is a fixed 15-second delay between the engagement of each electric heat stage. Each electric heat 
stage must be engaged for 1 minute (minimum ON timer) and each stage cannot be re-engaged for 1 minute 
after being switched OFF (minimum OFF timer). These delays are built into the unit controller. 
When the space temperature falls below the heating setpoint, electric heating shall be staged on to maintain 
the space temperature. The face & bypass damper shall fully open (face) when an electric heat stage is 
engaged. A proportional-integral control loop and built-in digital sequencer shall be used to control up to 3 
stages of electric heat. When the space temperature exceeds the heating setpoint, all electric heat stages 
shall be staged OFF. 
If the discharge air temperature falls below 52°F, all electric heat stages are immediately. All electric heat shall 
remain ON until the discharge air temperature rises above 55°F. 
If the discharge air temperature exceeds 130°F, all electric heat stages shall be immediately disengaged, 
regardless of the space temperature or the minimum ON timer. Electric heating shall remain disengaged until 
the discharge air temperature falls below 110°F. 
End-of-Cycle Valve Operation (Optional) 
A normally closed, 2-position valve with return on power failure is optionally used as a cooling end-of-cycle 
(EOC) valve. This valve prevents radiant effects from overcooling the space when the face & bypass damper 
is in the full bypass position. The EOC valve shall open when the face & bypass damper is commanded to 
open. 
The EOC valve shall be closed whenever the discharge air temperature falls below 55°F OR the coil low limit 
thermostat closes. The valve shall remain closed until the discharge air temperature exceeds 57°F AND the 
low limit thermostat opens. 
Outdoor Air Damper Control 
The outdoor air damper shall be closed in the unoccupied mode, regardless of the space temperature 
conditions. 
The outdoor air damper shall be closed in low limit conditions (See Safeties). 
The outdoor air damper shall be closed if the space temperature falls more than 3°F below the heating 
setpoint. The damper will not open until the space temperature rises within 2°F of the heating setpoint. 
The outdoor air damper shall be closed if the space temperature rises more than 3°F above the cooling 
setpoint. The damper will not open until the space temperature falls within 2°F of the cooling setpoint. 
The outdoor air damper shall close to minimum position when the outdoor air temperature exceeds 68°F 
The outdoor air damper shall be controlled with a proportional control loop based upon the deviation from 
setpoint. The outdoor air damper shall begin to modulate open from minimum position when the space 
temperature exceeds the (space setpoint - 0.5°F). The outdoor air damper shall be fully open when the space 
temperature rises 1.5°F above the setpoint. Except as noted in the paragraphs above, the outdoor air damper 
shall not close beyond minimum position during occupied operation. 
Safeties - Low Limit Conditions 
If the low limit thermostat trips OR the discharge air temperature falls below 55°F, the unit enters low limit 
mode. This shall drive the outdoor air damper closed. In cooling mode, this shall force the face & bypass 
damper into full bypass position and the optional EOC valve shall close. If the discharge air temperature falls 
below 52°F, the all stages of electric heat shall be engaged. 
Electric heat shall return to normal control when the discharge air temperature exceeds 55°F.Normal unit 
operation shall resume when the discharge air temperature exceeds 57°F and the low limit thermostat opens. 
7/1/03  Part Number 011-200001-003 Page 18 










