Specifications

Current Ratings 24 VA at 24 Vac, pilot duty.
Universal Inputs
10KW Thermistor w/ 11KW Shunt Resistor -40
to 250 °F (-40 to 121 °C) range. TS-5700-850 or
equivalent.
Voltage 0 to 5 Vdc.
Current 0 to 20 mA requires an external 500 ohm shunt
resistor.
Digital Input Dry Contact. Detection of closed switch
requires less than 300 ohm. Detection of open switch
requires more than 1.5K ohm.
Analog Outputs
Current 0 to 20 mA. (Output load from 80 to 550 ohms).
Software Capabilities
LONMARK-compatible.
HVAC interoperability achieved through use of
LONMARK HVAC profiles.
Pre-packaged factory installed software customized
for optimum unit operation.
Communications
LONWORKS Networks
A LONWORKS
communications network uses an FTT-10 Free Topology
configuration. Controllers on a LONWORKS network can
communicate with each other in a peer-to-peer fashion,
and connect to the WorkPlace Tech Tool software
platforms via the LON Jack on any LonMark controller or
on any MN-Sx sensor. The wall sensor must be
connected to the LON network. A LONWORKS network
has acommunications speed of 78k baud, using
unshielded,twisted-pair cabling.
S-Link A Sensor Link (S-Link) communications wiring
provides power and communication interface to the I/A
Series MicroNet sensor (MN-SX series). It uses two-wire,
unshielded cable and is not polarity sensitive. From some
sensor models, the user can view and adjust application
parameters. Maximum wire length allowed between a
controller and the I/A Series MicroNet Sensor is 200 ft.
(61 m).