User manual
FIBRE-to-SAS/SATA RAID SUBSYSTEM
150
User Manual
Controller Firmware Upgrade Table:
New
Original
1.11 1.20 1.21 Æ 1.30 Remarks
1.01 Yes Yes Yes
From 1.01 to
1.20, or 1.21 to
1.30; need to
reassign IP
1.09 Yes Yes Yes V3 controller
1.10 Yes Yes Yes V3 controller
1.11 No Need Yes Yes V3 controller
1.20 No Need No Need Yes
V3 and V4
controller
Detailed Steps for Upgrading Firmware to Version 1.30:
1. Uninstall current version of proRAID Manager.
A. Go to the installation directory of proRAID Manager and run the Uninstall
program.
2. Install the new proRAID Manager version 1.5.35.
A. Insert install CD.
B. Select the proRAID Manager version for your OS and download the installation
files.
C. Run the install program Install.exe.
3. Upgrade the proSES Firmware.
Check proSES board version installed in your system. Each proSES board
version is upgraded differently. PRO-90-6601 is SES version 1 and PRO-90-
5601 is SES version 2. The LCD will display “SES” for SES version 1 (PRO-90-
6601) and “SES2” for SES version 2 (PRO-90-5601).
Another way to check proSES board version is to remove the SES module
(need to power off the system) and check the version labeled on the PCBA.