Installation Owner's manual

MOD 30ML Multiloop Controller
MODULAR I/O CONNECTIONS
4.4.4 2011A Dual Mechanical Relay Outputs (DDOM)
Make mechanical relay output connections as shown in Figure 4-14. Output specifications
are:
DUAL MECHANICAL RELAY OUTPUTS
Configuration Dual relays (NO/NO, NC/NC, NO/NC)
Power supply range + 5 VDC ±10%
Max Input Current -10.0 mA DC
Contact load 3A at 60 VAC or 30 VDC
Contact resistance 0.10 ohms maximum
Isolation 250 Vrms (contacts to coil)
Current rating 3A per relay
Response time 10 msec
70