Installation Owner's manual
MOD 30ML Multiloop Controller
MECHANICAL INSTALLATION
24
Table 2-1. Module Types and Valid Locations
Module Type Data Base
Block Type
Module
Width
Module Location
2001A Voltage Input
2002A Current Input
VCIM Single Any Location
2012A Current Input with 2-Wire Transmitter VCIM Single (Note 4)
2003A Current Output AOM Single (Note 4)
2004A Solid State Relay Input DIM Single S1 through S6
(Note 1)
2005A Solid State Relay Output DOM Single S1 through S6
(Note 1)
2006A Nonisolated Digital Input DIM Single Any Location
2007A Nonisolated Digital Output DOM Single Any location
2009A RTD Input (2 Wire) RIM Single Any Location
2009A RTD Input (3 Wire) WRIM Double Any pair of Locations
2011A Mechanical Relay Output (SPST)
2011A Mechanical Relay Output (Form C)
DDOM
WDOM
Double
S1 & S2, S3 & S4,or
S5 & S6(Note 2)
2013A Thermocouple Input
with Upscale Burnout Detection
TIM Single Any Location
2020N Remote I/O Interface Module (discontinued) RIO Double Any Pair of Locations
2030N ICN Communication ICN Double S7&S8 (Port 2)
or
S9&S10 (Port 1)
(Note 3)
2032N RS-485 2-Wire Modbus Communication
(discontinued)
MSC Single S8 (Port 2) or
S10 (Port 1)
(Note 3)
2033N RS-232 Modbus Communication
2034N RS-485 4-Wire Modbus Communication
MSC Double S7 & S8 (Port 2)
or
S9 & S10 (Port 1)
(Note 3)
* NOTES: 1. The maximum working voltage between adjacent terminal of circuits
rated less than 30 V rms or 42.4 V peak or 60 Vdc must not be more
than 150 V. The maximum working voltage between adjacent terminal of
circuits rated greater than 30 V rms or 42.4 V peak or 60 Vdc must not
be more than 300 V.
2. If I/O circuit voltage is 30V rms, 42.4V peak, 60V dc or less, location
pairs S7-S8 and S9-S10 can also be used.
3. If a communications module is installed in location S10, built-in
communication drivers are not available.
4. Though 2003A and 2012A modules can be installed in any location,
special attention should be given to ensure adequate air flow for heat
dissipation. Refer to the I/O Module Planning section of this manual for
details.