Maintenance for 2001N, 2002N, and 1800R Manual
MOD30ML and Modcell Maintenance
VIEWING DIAGNOSTIC DATA
Table 3 .8. Status Window Commands
Command Description Equivalent
Command
ACK_SD Acknowledge shutdown fault W IF1,CMD 1
UP_MOD Upload to module W IF1,CMD 2
DOWN_MOD Download from module W IF1,CMD 3
SET_WP Set module write protect W IF1,CMD 4
CLR_WP Clear module write protect W IF1,CMD 5
DEL_MAIN Delete main data base W IF1,CMD 6
RES_MAIN Restore main data base W IF1,CMD 7
RESET Restart instrument after task completes W IF1,CMD 8
KILL Restart instrument before completing task W IF1,CMD 9
CLR_MT Clear maximum execution times W IF1,CMD 10
CLR_Q Clear system event queue W SE1,CLRQCMD 1
ACK_ALL Acknowledge all diagnostics, notification/
request messages, and process alarms
W SE1,GLBACK 1
ACK_DIAGS Acknowledge all diagnostics W SE1,DGACK 1
ACK_ALMS Acknowledge all process alarms W SE1,PAACK 1
R TIME
R DATE
R DAY
Read instrument time of day (Time includes
Date and Day or they can issued separately)
Read instrument calendar date
Read instrument day of week
R IF1,TIMEDAY
R IF1,DATE
R IF1,DAY
R IOLOCK Read instrument I/O Lock status R IF1,IOLOCK
R STATE Read instrument state R IF1,INSTATE
W TIME data
Write instrument time of day
W IF1,TIMEDAY data
W DATE data
Write instrument calendar date
W IF1,DATE data
W DAY data
Write instrument day of week
W IF1,DAY data
W STATE data
Write instrument state
W IF1,NXTISTAT data
R FG Read Minimum Foreground None
R FGO lsp
Read Foreground offset of attribute None
R BLOCK blkocc#
Read block and display bytes in hex None
R VERSION 1 Read instrument version None
R SD type 2
Read instrument shutdown area type None
R lsp
Read specified attribute None
R lsp type 3
Read Byte Before attribute None
RS lsp
Read specified string attribute
(RS IF1,USRTAG) None
RS lsp type 3
Read Byte Before string attribute
(RS EX1,13 H) None
W lsp data
Write specified attribute None
W lsp data type 3
Write Byte Before attribute None
ACK blkocc# diag# 4
acknowledge diagnostic point (e.g. ACK IF1
9)
None
NOTES for Table 3.8:
1. R VERSION command applies to any instrument on the network (ICN or Modbus) and is
returned as follows (current versions are bold, MOD 30 instruments start with C, R, A, or S
version id return data):
Description Return Data
2001P MODCELL Logic Controller Version 6 BxA__6xxxxxxx
(Version 1, 2, 3, 4, 5 follow in same fashion) BxA__...
2002P MODCELL Regulatory Controller Version 3 DxA__3xxxxxxx
(Version 1, 2 follow in same fashion) DxA__...
3 -27