Maintenance for 2001N, 2002N, and 1800R Manual

Technical Notice
Wiring
When using a dedicated instrument ground, the resistance to ground should be less than 1 ohm.
Use stranded wire for best noise immunity, of sufficient gauge to keep the resistance low. For
example, at least 18 AWG (1.02 mm) wire would be required for a distance of 150 feet, or 10 AWG
(2.6 mm) for 1000 feet.
Since instrument common terminals 25, 16 and 41 are all internally tied together, 16 and 41 will also
be tied to ground when terminal 25 is connected to ground.
If necessary, use a “pigtail” wire from the terminal and splice it to multiple common or shield wires.
Spliced wires should be twisted before applying a crimp connector.
All ground wires should be kept as short as possible.
DO NOT use the wire’s shield for a signal or common.
Analog input signal wiring must be at least 22 AWG (0.65 mm), though larger is perferred.
Wire Recommendations:
Stranded shielded twisted pair wire should be used for all signal and communication wiring. The wire
should have a minimum of a 2-inch lay (6 twists per foot). It is best for each pair to have its own
shield. If using multiple pairs that share a shield, do not mix high and low voltage signals within the
same shield.
I/O Signals
At least 22 AWG (0.65 mm), though larger is perferred
Remote I/O Communications
Up to 1600 ft (500 m) 24 AWG (0.51 mm) overall foil shield and drain wire
(Beldon 9841 or equiv.)
ICN Communications
Up to 500 ft (150 m) 18 AWG (1.02 mm)
500-1500 ft (150-460 m) 18 AWG (1.02 mm), 18-25 pf/ft (60-83 pf/m)
1500-2000 ft (460-610 m) 22 AWG (0.64 mm)
RS-232 Communications
Up to 50 ft (15 m) virtually any standard shielded twisted pair with drain
(Beldon 9502 or equivalent)
RS-422 and RS-485
Up to 20 ft (6 m) virtually any standard shielded twisted pair with drain
20-1000 ft (6-305 m) 24 AWG (0.51 mm) overall foil shield and drain wire
(Beldon 9841 for 2-wire and 9502 for 4-wire, or equiv.)
1000-4000 ft (305-1220 m) 24 AWG (0.51 mm) overall foil shield and drain wire on each pair
(Beldon 9841 for 2-wire and 9729 for 4-wire, or equiv.)
Topic: MOD 30ML/Modcell Technote: TNML1001-1
MicroMod Automation, Inc. Rev. 3, Feb-2005
GroundingWiring.doc Page 3 of 4