Front Face Configuration Lab Part 3 – Module Configuration
5 -7
• Using the and pushbutons, move the pointer to the IR parameter and press
F3.
• The display screen now shows the IR parameter
Figure 5.8
Control Module
Instrument Range
configuration
display
• The IR is changed by using the / buttons to select the digit and then use the /
/ to modify the value of the digit. Change the value to 300.
• Press F3 to accept this value. The display is returned to the General CON
parameter list. The new IR value is displayed.
• Visually check the value of the IRL parameter. If this value is not 0.0, use the
/ pushbutons to move the pointer to the IRL parameter and press F3.
• The IRL is changed by using the / buttons to select the digit and then use the
/ to modify the value of the digit. Change the value to 0.