Instruction Manual
7.3 RS-232/485 ITB-PLC CABLE
A custom RS-232 cable is required for connection from the RS-232/485 ITB J1 to the PLC. The
recommended cable for this PLC application is illustrated in Figure 7-2. In the figure, one end of
the cable has a 9 pin female connector for J1 of the RS-232/485 ITB and the other end has a 25
pin male or female plug as required by the PLC.
The typical maximum cable length for this RS-232 connection is 50 feet (15.2 m).
RS-232/485 ITB, J1 SIEMENS PLC
(FEMALE DB-9 (MALE/FEMALE, DB-25
CABLE END) CABLE END) (MODELS
DL405 AND DL305
WITH DCU)
RxD (IN) 2 2 TxD (OUT)
TxD (OUT) 3 3 RxD (IN)
GND 5 7 GND
74 RTS
85 CTS
Figure 7-2. RS-232/485 ITB J1 to Siemens PLC Cable
53MC9015 53MC5000 PLC and Printer Interfaces
7-2
SIEMENS