Instruction Manual
Table 5-3. OPTOMUX Digital I/O Control Bytes
Title DDI-A DDI-B Set By Default
Communication Mode - A minimum of one word (16 L-
values) is transferred even if only one L-value is used as
an active indicator of a process event.
0 = No data exchange
1 = Reads only - (PCS ⇐ board).
2 = Reads and writes - (PCS ⇔ board)
3 = Writes only - (PCS ⇒ board)
B664 B640 User 0
Number of Contiguous Active Boards 00-15 B665 B641 User 0
Number of Contiguous Active Boards 16-31 B666 B642 User 0
Number of Contiguous Output Modules for Even Board
Addresses 00-15
B667 B643 User 0
Number of Contiguous Output Modules for Odd Board
Addresses 00-15
B668 B644 User 0
Number of Contiguous Output Modules for Even Board
Addresses 16-31
B669 B645 User 0
Number of Contiguous Output Modules for Odd Board
Addresses 16-31
B670 B646 User 0
Watchdog Delay on Outputs (PCS ⇒ board) of Each Board
Address 00-15:
0 - Watchdog disabled
1 - After 10 seconds, turn-off all outputs.
2 - After 1 minute turn-off all outputs.
3 - After 10 minutes turn-off all outputs.
4 - Watchdog timer disabled.
5 - After 10 seconds turn-on output 0, turn-off all other
outputs.
6 - After 1 minute turn-on output 0, turn-off all other
outputs.
7 - After 10 minutes turn-on output 0, turn-off all other
outputs.
B671 B647 User 0
Watchdog Delay on Outputs (PCS ⇒ board) of Each Board
Address 16-31 - the description is the same as
Addresses 00 - 15.
B672 B648 User 0
53MC9015 53MC5000 PLC and Printer Interfaces
5-10
OPTO