Instruction Manual Owner's manual

Table D-14. Database - L Type Datapoints
Data-
point
Name Module Atom Default Table
L000 Discrete Input 0 (Standard)
DI
DI0 0
5-6
L001 Discrete Input 1 (Standard) DI1 0
L002-
L017
Discrete Inputs 2 through 17
(Optional)
DI2-
DI17
0
L018-
L023
Discrete Inputs 18 through 23
(Optional)
DI18-
DI23
0
L024 Discrete Output 0 (Standard)
DO
DO0 0
5-7
L025 Discrete Output 1 (Standard) DO1 0
L026-
L041
Discrete Outputs 2 through 17
(Optional)
DO2-
DO17
0
L042-
L047
Discrete Outputs 18 through 23
(Optional)
DO18-
DO23
0
L048 Remote/Local Push Button Pressed RLPB 0
L049 SP Increment Push Button Pressed SPIPB 0
L050 SP Decrement Push Button Pressed SPDPB 0
L051 Auto/Manual Push button Pressed AMPB 0
L052 Output Increment Push Button
Pressed
OVIPB 0
L053 Output Decrement Push Button
Pressed
OVDPB 0
L054 F1 Push Button Pressed FNC1PB 0
L055 F2 Push Button Pressed FNC2PB 0
L056 F3 Push Button Pressed FNC3PB 0
L057 Function 1 (F1) Foreground Oneshot FNC1FO 0
L058 Function 2 (F2) Foreground Oneshot FNC2FO 0
L059 Function 3 (F3) Foreground Oneshot FNC3FO 0
L060 Function 1 (F1) Background Oneshot FNC1BO 0
L061 Function 2 (F2) Background Oneshot FNC2BO 0
L062 Function 3 (F3) Background Oneshot FNC3BO 0
L063 No Alarm Line Annunciation System NALIN 0
L064 Silence (Goes to 1 when Horn = 1
and the Acknowledge Push Button
is Pressed)
SILENCE 0
L065 Horn (Goes to 1 on Alarm Entry) HORN 0
L066 Power Up (Goes to 1 on Reset) System PWRUP 0
L067 Power Failure Time (Goes to 1 for
Short Term Power Failure)
PFT 0
L068 Peer-to-Peer Task Failure PPF1 0
L069 Peer-to-Peer Task Failure
(n-1)
PPF2 0
L070 0 0
L071 1 1
L072 Remote Keypad Enable RMTK 0
L073 Standard Log Run SLR
1 of 6
Appendix D. Database
D-11