6.4.17.2 Vector control with encoder (VC)
¾ First step: Parameterizing the speed encoder (refer to Section 6.4.15)
¾ When commissioning Vector Control with encoder-feedback (VC), the drive
should be configured for V/f mode (see p1300) first. Run the drive and compare
r0061 with r0021 that should agree in:
sign
magnitude (with a deviation of only a few percent)
Only if both criteria are fulfilled, change p1300 and select VC (p1300 = 21/23).
¾ Encoder loss detection must be disabled (p0492 = 0) if torque is limited
externally., e.g.:
closed-loop winder control
traversing / moving to a fixed endstop
when using a mechanical brake
Control mode
21 Vector control with sensor
Filter time for act. speed
Sets time constant of PT1 filter to smooth actual speed of speed controller.
Decreasing the value leads to a higher dynamic of the speed regulation. Instability is seen if
the value is to low. p1442 = 2 can be set for most applications.
Gain speed controller
Enters gain of speed controller.
Integral time speed controller
Enters integral time of speed controller.
Precontrol
Freq. setpoint
r1438
r1084
Kp Tn
p
1
4
6
0
p
1
4
6
2
r0064
Torque
setpoint
p
1
4
9
6
p
0
3
4
1
p
0
3
4
2
p
1
4
4
2
Act. frequency
from encoder
r0063
r1170
p1492
p
1
4
8
9
p
1
4
8
8
Droop
r1490
150 ms
r1518
0
1
0
r0079r1508
*) only active, if pre-control is enabled
(p1496 > 0)
*)
P1300=21
0
4 ms
3.0
P1442 = ...
P1460 = ...
P1462 = ...
400 ms