5. Warm beer A. Defective Pump (check
motor also)
A. Check return line in reservoir
for liquid flow. Replace pump
B. Defective motor (check pump
also)
B. Replace motor
C. Refrigeration unit not running C. Refer to 2
D. Conduit lines located in over-
heated area
D. Remove from any hot water
pipes or kitchen area with
stove or glass washer.
E. Conduit lines flooded in PVC
chase.
E. Remove lines from PVC,
thoroughly dry PVC and
repair or replace conduit as
needed.
F. Uninsulated or poorly insu-
lated lines
F. All lines should be fully insu-
lated from cooler into dis-
penser. Includes glycol lines
from power pack into cooler.
G. Thermostat G. Adjust temperature to colder
setting.
H. Condenser fan motor not
working
H. Replace condenser fan
motor.
I. Freon leak I. Repair leak and recharge.
J. Dirty condenser J. Clean the condenser
K. Condensation inside conduit
insulation (may be caused
from cleaning lines)
K. Check trunk housing in areas
for drooping or low spots,
split insulation approxi-
mately 5” and separate.
Allow any water to drain,
then air dry, the seal closed.
L. Warm walk in cooler L. Check temperature of walk-in
cooler-liquid temperature, set
cooler at 36° to 38°.