Operating instructions

TM 11574A-OI
2-54
(e) compressor and condenser fan motors. The cool light is also de-energized.
(f) The evaporator fan motors continue to run to circulate air throughout the container. The
in-range light remains illuminated as long as the supply air is within tolerance of set point.
(g) When the supply air temperature increases to 0.4 F (0.2 C) above set point and the three
minute off time has elapsed, relays TC and TN are energizes to restart the compressor
and condenser fan motors. The cool light is also illuminated.
(2) Sequence Of Operation – Perishable Mode Heating
NOTE
The unit will heat only when in the Perishable Mode, relay TH is electronically locked out
when in the Frozen mode.
(a) If the air temperature decreases 0.9 F (0.5 C) below set point, the system enters the
heating mode (see Figure 4-13). The controller closes contacts TH (see Figure 2-21) to
allow power flow through the heat termination thermostat (HTT) to energize the heaters
(HR). The HEAT light is also illuminated. The evaporator fans continue to run to
circulate air throughout the container.
(b) When the temperature rises to 0.4 F (0.2 C) below set point, contact TH opens to de-
energize the heaters. The HEAT light is also de-energized. The evaporator fans
continue to run to circulate air throughout the container.
(c) A safety heater termination thermostat (HTT), attached to an evaporator coil support, will
open the heating circuit if overheating occurs.
Figure 2-20. Perishable Mode Cooling.