Operating instructions

TM 11574A-OI
C-3/(C-4 Blank)
COMPRESSOR DOES NOT RUN
Main power line open – replace fuse or reset
circuit breaker
Safety thermostat tripped – reset thermostat
Control stuck open – replace control
Loose terminal connections – check connections
Improperly wired controls - Check wiring and
rewire
Low line voltage – Check line voltage. Determine
location of voltage drop
Compressor motor defective – Check motor
winding for open or short. Replace compressor if
necessary
Seized compressor – Replace compressor
COMPRESSOR CYCLES ON LOW PRESSURE
CONTROL
Low pressure control erratic in action – Raise
differential setting, check capillary for pinches,
replace control
Suction shutoff valve partially closed – Open
valve
Low refrigerant charge – Add refrigerant
Plugged suction strainer – Clean strainer
Defective TXV – Replace TXV
COMPRESSOR
CYCLES ON HIGH PRESSURE
CONTROL
High pressure control erratic in action – check
capillary tube for pinches, Set control as required
Discharge valve partially closed – Adjust valve
Air in system – recover
Condenser scaled (or airflow restricted) – Clean
condenser
Refrigerant Overcharge – Recover
INSUFFICIENT CAPACITY
Low refrigerant charge – Add refrigerant
Control set too high – reset control
Expansion valve plugged – clean or replace
Inefficient compressor – check valves and pistons
Expansion valve setting too high – lower setting
Iced or dirty evaporator – defrost or clean
UNIT OPERATES LONG OR CONTINUOUSLY
Low refrigerant charge – Add refrigerant
Control contacts fused – replace controls
Air in system – recover
Partially plugged or plugged expansion valve or
strainer – clean or replace
Defective insulation – replace or repair
Service load – Keep doors and windows closed
Inefficient compressor – check valves
Condenser scaled – clean condenser
Restricted evaporator air –
defrost coil, clean filters
and ductwork
SYSTEM NOISES
Piping vibration – Support piping as required,
check for plugged liquid line strainer
Expansion valve hissing – add refrigerant, check
for plugged liquid line strainer
Compressor noisy – check valve plates for valve
noise, replace compressor (worn bearings), check
for loose compressor hold down bolts
Inefficient compressor oil – add oil
COMPRESSOR LOSES OIL
Leak in system – repair leak
Plugged or stuck compressor oil return check valve
repair or replace
Oil trapping in line – check piping for oil traps
FROSTED SUCTION LINE
Expansion valve admitting excess refrigerant –
adjust expansion valve
HOT LIQUID LINE
Shortage of refrigerant – repair leaks and recharge
FROSTED LIQUID LINE
Receiver shutoff valve partially closed or restricted
Open valve or remove restriction
Restricted strainer dryer – replace
FROSTED EXPANSION VALVE
Ice plugging TXV orifice – apply hot wet cloth to
TXV
Moisture indicated by increase in suction pressure –
install drier
Plugged TXV strainer – clean strainer or replace
TXV