Instruction manual

Pg. 19
www.incoe.com
©INCOE® CORPORATION 8/2010
2
M SERIES
INSTRUCTION MANUAL
OPERATION
A: To select the temperature unit (°C or °F).
B: To define a minimum setpoint.
C: To define a maximum setpoint.
D: To select a type of sensor (type J or type K).
E: To allow the automatic switch to manual
mode in case of thermocouple breakage. If
so, the last percentage of power calculated
by the CPU is applied to the zones with
broken sensors. If not, the power is cut and
the zone remains in automatic mode.
Press NEXT to access the second page for
configuration:
F: To enter the password to activate the
MoldScan option.


A
B
C
D
E
F
Key to select parameters
to be modified
A: To select the softstart mode: either ramp duration
(RT) or ramp rate (RR).
B: To select ramp duration with unit °F/minute (if
selected before).The temperature is raised every
minute by a preset number of degrees. The
percentage of power applied is not limited. When
actual temperature reaches setpoint, the ramp is
over. Its duration depends on the gap between
setpoint and actual temperature value as well as
the temperature increase per minute selected.
C: To define the ramp duration in minutes (if this
mode was selected).
D: To define the maximum power applied during the
softstart phase (in %).
E: To define the duration of the BOOST function (in
seconds).The principle of the BOOST function
is to increase or decrease setpoint of all zones
during a programmable period of time.