OPERATION
2.6 SAFETY CONDITIONS
M Series cabinets are fitted with:
- circuit breaker for tool protection.
- electronic circuit for monitoring of voltage for
device protection against faulty and overvoltage
(10% of extra power is admissible).
- Venting, filter (must be cleaned frequently to
prevent damage).
Each power control card 16A or 5A is protected by:
- The power control card is protected if supply
voltage exceeds 275 V.
- Quick blown fuses on all phases and neutral protect
the TRIAC against overcurrent draw.
2.7 THERMOCOUPLES
Temperature sensors are connected on the male
HARTING plug (in case of a non-mixed wiring
diagram) located on backside of cabinet. Thermocouples
of J type (Iron-Constantan), or K (Ni.Cr/NiAL), or
auxiliary inputs can be connected. Conform to
polarity diagram as indicated on the wiring diagram.
Some standards define colours for thermocouple
leads, for instance:
J sensors (+ = Iron, - = Constantan):

Iron: Yellow / Constantan: Black

Iron: Red/ Constantan: Blue

Iron : Yellow / Constantan: Blue

Iron: Black / Constantan: White

Iron: White / Constantan: Red
‘’+’’ is Iron and can easily be identified with a
magnet.
K sensors (+ = Chrome or Nickel-Chrome, -
= Alumel or Nickel-Aluminium):

Chromel: Yellow / Alumel: Blue

Chromel: Red / Alumel: Green

Chromel: Red/ Alumel: Blue

Chromel: Green / Alumel: White

Chromel: Yellow/ Alumel: Red
Wires between J or K thermocouples and connectors
on backside of cabinet must made of the same metal
as the sensor (compensation leads) in order not to
introduce parasite thermocouples.
Wiring diagram according to INCOE standard:
BASE FOR THERMOCOUPLE 48 pins 16A
Type HARTING HAN E WITH MALE INSERT.