7. Module: ECAN™ Technology
Under specific conditions, the first five bits of a
transmitted identifier may not match the value in
the Transmit Buffer ID register, TXBnSIDH. The
following conditions must exist for the corruption
to occur:
• A transmit message must be pending
• The ECAN module must detect a
Start-of-Frame (SOF) in the third bit of the
interframe space.
Work around
None.
Affected Silicon Revisions
8. Module: ECAN Technology
The Error Interrupt Flag, ERRIF (PIR3<5>), may
not be able to be cleared in software after either
of the following counter registers exceeds 127:
• Transmit Error Counter Register (TXERRCNT)
• Receive Error Counter Register (RXERRCNT)
Work around
Monitor the EWARN (COMSTAT<0>) bit to
determine if either the TXERRCNT or the
RXERRCNT exceeds 95 and clear the ERRIF
flag before either counter reaches 127.
Affected Silicon Revisions
9. Module: ECAN Technology
Following an error on the bus, the ECAN module
is unable to switch from Listen Only mode
directly to Configuration mode.
Work around
Use the REQOP (CANCON<7:5>) bits to select
Normal mode as an intermediate step when
switching from Listen Only mode to Configuration
mode.
Affected Silicon Revisions
A1 B0 B2
X
A1 B0 B2
X
A1 B0 B2
X