Specifications

66
When using the manual air control timer mode: Door 1 (damper 1) is open, door
2 (damper 2) is closed and door 3 (damper 3) is open. When using the
automatic energy-save mode: If the system calls for central air conditioning and
the outside air meets conditions then door 1 (damper 1) is open, door 2 (damper
2) is closed and door 3 (damper 3) is open.
In the automatic fresh air mode: If the fresh air minimums have not been met:
door 1 (damper 1) is open, door 2 (damper 2) is closed and door 3 (damper 3) is
open. The central air AC air blower fan is turned on and door 4 (damper 4) is
opened to blend in controlled amounts of fresh air between air exchanges.
Fresh air mode involves the main control unit making a decision to introduce new
air into the building from outside. This has many advantages including removing
stagnant air that has been inside the building along with any pollutants it has
picked up while in the building. In typical HVAC systems, the air inside the
building is repeatedly cooled and redistributed in the building. This means the
only way to introduce fresh air into the building is to open windows. Opening and
closing windows is a hassle for the occupants of the building because they must
be closed when the building is unoccupied, and in larger buildings opening the
windows is not always an option. Figure 24 pictured below is an air duct with a
damper motor assembly. This particular duct was removed due to a defective
damper.
Approx. 4'
Figure 24 Air duct with damper motor assembly
Dampers can be operated by two different distinct modes either manual or
automatic. These electronic zone dampers are often referred to as a Volume
Control Damper (VCD). Automatic dampers are the type of dampers we are
going to use in our design, whereas manual dampers function by turning a