RFT9739 Rack-Mount Transmitter Instruction Manual
Output Wiring
continued
5.8 Remote-zero switch
The transmitter can be zeroed from a remote switch. If the transmitter
display indicates flow rate, this contact will zero the flowmeter. If the
transmitter display indicates flow total, this contact will reset the flow
total.
Section 6.4
, page 65, describes the flowmeter zeroing procedure.
Section 6.5
, page 67, describes the totalizer reset procedure.
The switch must be a momentary-type contact, normally open, close to
zero, and must carry 1 mA of current in the closed position. The open
circuit voltage is 5 VDC.
Use terminals CN2-D20 and CN2-D26 for the remote switch. Terminal
D26 serves as a common return for the external-switch input,
frequency/pulse output, dual-channel frequency output, and control
output. See
Figure 5-28
.
Figure 5-28.
Wiring to remote-zero
switch
Remote
switch
RFT9739
output terminals
ZERO+ (signal line)
RETURN (ground)