Instruction manual
Output Wiring
continued
RFT9739 Field-Mount Transmitter Instruction Manual
35
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
Power-Supply and
Sensor Wiring
5.5 Control output
The control output can indicate flow direction, transmitter zeroing in
progress, pressure input failure, faults, event 1 or event 2. For
information on configuring the control output for events, see any of the
following manuals or AMS on-line help:
•
Using the HART Communicator with Micro Motion Transmitters
•
Using ProLink Software with Micro Motion Transmitters
•
Using Modbus Protocol with Micro Motion Transmitters
Use RFT9739 terminals 22 and 16 for the control output. The control
output, frequency/pulse output, and external zero input share terminal
16 as a common return. See
Figure 5-10
.
• When configured to indicate flow direction, the output is high (+15 V)
when indicating forward flow, and low (0 V) when indicating reverse
flow.
• When configured to indicate transmitter zeroing in progress, the output
is low (0 V) when zeroing is in progress and high (+15 V) at all other
times.
• When configured to indicate faults, the output is low (0 V) when a fault
condition exists and high (+15 V) during normal operation.
• When configured to indicate event 1 or event 2, the output switches ON
(0 V) or OFF (+15 V) when the flow rate, flow total, density,
temperature, or pressure of the process fluid achieves a programmed
setpoint.
• The output circuit is rated to 30 VDC, with 0.1 ampere maximum
sinking capability, when used in open collector mode. Open collector
mode is described on page 36.
• Transmitter output is nominal 0 or +15 V, unloaded.
• Output impedance is 2.2 kohm.
Figure 5-10. Control output wiring
RFT9739
output terminals
RETURN (ground)
CONTROL (signal line)