Instruction manual

Output Wiring
continued
RFT9739 Field-Mount Transmitter Instruction Manual
35
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
Power-Supply and
Sensor Wiring
5.5 Control output
The control output can indicate flow direction, transmitter zeroing in
progress, pressure input failure, faults, event 1 or event 2. For
information on configuring the control output for events, see any of the
following manuals or AMS on-line help:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with Micro Motion Transmitters
Use RFT9739 terminals 22 and 16 for the control output. The control
output, frequency/pulse output, and external zero input share terminal
16 as a common return. See
Figure 5-10
.
• When configured to indicate flow direction, the output is high (+15 V)
when indicating forward flow, and low (0 V) when indicating reverse
flow.
• When configured to indicate transmitter zeroing in progress, the output
is low (0 V) when zeroing is in progress and high (+15 V) at all other
times.
• When configured to indicate faults, the output is low (0 V) when a fault
condition exists and high (+15 V) during normal operation.
• When configured to indicate event 1 or event 2, the output switches ON
(0 V) or OFF (+15 V) when the flow rate, flow total, density,
temperature, or pressure of the process fluid achieves a programmed
setpoint.
• The output circuit is rated to 30 VDC, with 0.1 ampere maximum
sinking capability, when used in open collector mode. Open collector
mode is described on page 36.
• Transmitter output is nominal 0 or +15 V, unloaded.
• Output impedance is 2.2 kohm.
Figure 5-10. Control output wiring
RFT9739
output terminals
RETURN (ground)
CONTROL (signal line)