Instruction manual
22
RFT9739 Field-Mount Transmitter Instruction Manual
Power-Supply and Sensor Wiring
continued
The wiring procedure is the same for the sensor and transmitter. Refer to
the hazard statements on page 21 and the wiring diagrams below and
on page 23, and follow these steps:
1. Insert the stripped ends of the individual wires into the terminal
blocks. No bare wires should remain exposed.
• At the sensor, connect wiring inside the sensor junction box.
• At the transmitter, connect wiring to the transmitter's intrinsically
safe terminals for sensor wiring, as numbered in
Table 4-1
.
Transmitter terminal blocks can be unplugged for easier connection
of wiring.
2. Locate the wires by color as indicated in
Table 4-1
.
3. Tighten the screws to hold the wires in place.
4. Tightly close the sensor junction-box cover and transmitter housing.
On an ELITE sensor junction box, tighten all four cover screws.
Table 4-1.
Terminal designations
Figure 4-5. Wiring to ELITE
®
CMF sensors
Wire
color
Sensor
terminal
Transmitter
terminal Function
Black*
*Combined drain wires from brown/red, green/white, and gray/blue pairs, and
yellow/orange/violet triplet.
No connection 0 Drain wires*
Brown11Drive +
Red22Drive –
Orange 3 3 Temperature –
Yellow 4 4 Temperature return
Green 5 5 Left pickoff +
Blue 6 6 Right pickoff +
Violet 7 7 Temperature +
Gray 8 8 Right pickoff –
White 9 9 Left pickoff –
Green
White
Brown
Violet
Yellow
Orange
Blue
Gray
Red
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
ELITE
®
sensor
terminals
Flowmeter
cable
Field-mount
RFT9739 terminals
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Brown
Orange
Green
Violet
White
Gray
Blue
Yellow
Red
Black (Drains)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the
instructions that are shipped with the cable