Instruction manual
Power-Supply and Sensor Wiring
continued
RFT9739 Field-Mount Transmitter Instruction Manual
21
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
Power-Supply and
Sensor Wiring
4.3 Sensor wiring
The instructions in this section explain how to connect a fully prepared
Micro Motion flowmeter cable to the RFT9739 and a sensor. The sensor
can be a Micro Motion ELITE, F-Series, Model D, DT, or DL sensor.
• The procedure for preparing Micro Motion flowmeter cable and cable
glands is described in the instructions that are shipped with the cable.
• Install cable and wiring to meet local code requirements.
• Use Micro Motion color-coded cable.
• Total length of cable from the sensor to the transmitter must not exceed
1000 feet (300 meters).
Cable connections to
sensor and transmitter
WARNING
Operating the transmitter without covers in place
exposes electrical hazards that can cause property
damage, injury, or death.
Make sure the safety barrier partition, electronics module
cover, and housing cover are securely in place before
operating the transmitter.
CAUTION
Failure to seal sensor junction box and transmitter
housing could cause a short circuit, which would
result in measurement error or flowmeter failure.
To avoid risk of condensation or excessive moisture in the
junction box or transmitter housing:
• Seal all conduit openings.
• Install drip legs in conduit or cable.
• Ensure integrity of gaskets and O-rings, and fully tighten
all housing covers.
CAUTION
Improper installation of cable or conduit could cause
inaccurate measurements or flowmeter failure.
Keep cable away from devices such as transformers,
motors, and power lines, which produce large magnetic
fields.