Instruction manual
16
RFT9739 Field-Mount Transmitter Instruction Manual
Power-Supply and Sensor Wiring
continued
The base of the transmitter has three ¾-inch NPT female conduit
openings, indicated in
Figure 4-1
, which must remain sealed to keep the
transmitter watertight.
• Use conduit that allows a complete seal with the conduit openings.
• If possible, orient the transmitter with its conduit openings pointed
downward. Seal the conduit to prevent condensation and other
moisture from entering the housing.
• To comply with requirements for explosion-proof installations approved
by UL or CSA, install approved explosion-proof conduit seals on all
three conduit openings.
• To comply with CENELEC requirements for installations in Europe, see
page 17.
Figure 4-1. RFT9739 exploded view
Hinged cover of
electronics module
Intrinsically safe
terminals for wiring
to sensor
Partition (safety barrier)
Must be in place during
operation of transmitter
Housing base
Sensor wiring
conduit opening
Power-supply
conduit opening
Electronics module
Non-intrinsically safe
output terminals
Power-supply wiring
and equipment ground
terminals
Output wiring
conduit opening