Instruction manual
Getting Started
continued
RFT9739 Field-Mount Transmitter Instruction Manual
5
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
Power-Supply and
Sensor Wiring
2.3 Switch settings
Switches 1 through 10 on the electronics module control the following
transmitter functions:
• Baud rate
• Stop bits and parity
• Data bits, communication protocol, and physical layer
• mA outputs
• Zeroing method
• Write-protection of transmitter configuration
Switches 1 through 10 are illustrated in
Figure 2-2
, and described in the
following sections. Normally, switch settings do not require adjustment.
Security modes
Switches 1, 2, and 3 are security switches, which enable the user to
disable flowmeter zeroing, disable resetting of totalizers, and write-
protect all configuration and calibration parameters.
Switch settings enable any of eight possible security modes. Different
modes determine which functions are disabled and whether
configuration and calibration parameters are write-protected. The
following functions can be disabled:
• Flowmeter zeroing using digital communications
• Flowmeter zeroing using the zero button and, if the transmitter has a
display, the Scroll and Reset knobs
• Totalizer reset, with flow, using digital communications
• Totalizer reset, with flow, using the Scroll and Reset knobs, if the
transmitter has a display
• Totalizer control, with zero flow, using digital communications
• Totalizer control, with zero flow, using the Scroll and Reset knobs, if the
transmitter has a display
• Ability to change configuration or calibration factors
Table 2-1
lists the parameters that are write-protected and functions that
are disabled for each security mode. Security modes 1 through 7 are
entered immediately when switches 1 through 3 are set.
For information about security mode 8, see pages 6 through 8.
Figure 2-2. Switches
Switches 1 through 10 at left
are shown in the OFF position.