Operating instructions
MICRO PANEL XV-102 3.5" 5. Installation
M002869-02, 07/2009 35
RS485 topology #
##
# A bus segment can connect up to 32 bus stations.
#
##
# Several bus segments can be linked via repeaters (bidirectional amplifiers). Refer to the documen-
tation of the repeater manufacturer for further information.
#
##
# A bus segment must be provided with cable termination (120 Ω) at both ends. These terminations
must be connected directly between pin 3 and 7 in the connector.
!
The maximum cable length can be increased by using repeaters. Refer to the documen-
tation of the repeater manufacturer for further information.
!
#
##
# The bus segment must be terminated at both ends.
#
##
# No more than two terminations must be provided on each bus segment.
#
##
# Transmission faults can occur if operation is carried out without the correct termina-
tion.
Fig. 16 Termination
1
2
3
6
7
5
4
8
9
B
A
120