Operating instructions
5. Installation MICRO PANEL XV-102 3.5"
30 M002869-02, 07/2009
#
##
# The maximum baud rate depends on the cable length:
Tab. 12 Relationship of cable length / baud rate
CAN bus topology #
##
# A bus segment can connect up to 32 bus stations.
#
##
# Several bus segments can be linked via repeaters (bidirectional amplifiers). Refer to the documen-
tation of the repeater manufacturer for further information.
#
##
# A bus segment must be provided with cable termination (120 Ω) at both ends. These terminations
must be connected in the connector, directly between pin 2 and 7.
Cable length Max. baud rate
40 m 1000 Kbit/s
50 m 800 Kbit/s
100 m 500 Kbit/s
250 m 250 Kbit/s
500 m 125 Kbit/s
500 m 100 Kbit/s
1000 m 50 Kbit/s
2500 m 20 Kbit/s
5000 m 10 Kbit/s
!
#
##
# The use of repeaters is recommended with cables over 1000 m in length. Repeaters
can also be used to implement electrical isolation. Refer to the documentation of the
repeater manufacturer for further information.
#
##
# Observe the recommendations of the CiA (CAN in Automation).
#
##
# When preparing the cables, ensure that there is a low-resistance connection between
the cable shield and the connector casing (→ Chapter 5.3.2, "
""
" 23).
!
#
##
# The bus segment must be terminated at both ends.
#
##
# No more than two terminations must be provided on each bus segment.
#
##
# Transmission faults can occur if operation is carried out without the correct termina-
tion.
Fig. 12 Termination
1
2
3
6
7
5
4
8
9
CAN-H
CAN-L
120