5.3.3 Power supply
The device is provided with an internal fuse and is protected against polarity reversal. The GND terminal
is connected exclusively to the connector cover and not to the 0 V. The housing is made from plastic
and is isolated. The device power supply is not electrically isolated.
The device requires a 24 VDC power supply from an AC/DC converter with safe isolation (e.g. SELV).
For other power supply requirements see Chapter .
#
##
# SELV (safety extra low voltage):
Circuit in which no dangerous voltage is present, even in the event of a single fault.
Wiring
#
##
# Phoenix Contact MSTB 2.5/3-ST-5.08 connector, Phoenix order no. 1757022 is always supplied
with the device.
Tab. 5 Assignment of connector
#
##
# The following must be observed when the connector wiring is prepared:
Tab. 6 Preparing the wiring of the connector
Fig. 6 Power supply interface
Fig. 7 Phoenix Contact MSTB 2.5/3-ST-5.08 connector (view from the wiring side)
Connection Assignment
+24 VDC +24 VDC power supply
GND Functional ground connected with connector cover
(does not have to be connected)
0 V 0 V power supply
Preparing the wiring of the connector
Terminal type Pluggable screw terminal
Cross-section
#
##
# min. 0.75 mm
2
/ max. 2.5 mm
2
(lead or wire)
#
##
# min. AWG18 / max. AWG12
Stripping length 7 mm
GND 0 V+24 VDC