Troubleshooting guide
MAGNUM VERSION 8 MANUAL REVISION 3.1
90
Status of Boiler Logic displayed by MCS Connect
7.75.3.
The Boiler status is displayed by clicking on the Boiler tab:
Pump General Status:
Pump Capacity State: Pump state.
Time: Time in current pump state.
Step Delay: Seconds remaining before next pump adjustment is checked.
Rate of Change: Rate of change of the controlling sensor. In above example the control on water in has been
selected, sensor CTLT-IN.
Wanted/Actual/Available: Pumps wanted on = 1, actual =1, available =1. In above example there are 2
pumps but only 1 can be on at a time. The second pump is back up.
Wanted VFD%: Position of pump VFD if applicable.
VFD% Delay: Seconds remaining before next pump VFD adjustment is checked.
Pump Individual Status:
Pumps State: State of individual pumps.
Time: Time in current individual pump state.
Lead?: Indicates the lead pump.
Boiler Stage General Status:
Pump Capacity State: Boiler state.
Time: Time in current boiler state.
Step Delay: Seconds remaining before next boiler stage adjustment is checked.
Rate of Change: Rate of change of the controlling sensor. In above example the control on water in has been
selected, sensor CTLT-IN.
Wanted/Actual/Available: Pumps wanted on = 4, actual =4, available =4. In above example there are 4
boiler stages and all are on.
Boiler Individual Status:
Boiler State: State of individual boiler stages.
Time: Time in current individual boiler stages state.
Lead?: Indicates the lead boiler stage.
Status of Boiler Logic displayed by the Magnum
7.75.4.
The Boiler status is displayed by selecting the Status form the main menu. The Boiler/Pump information is the same as
above but it requires the following 4 screens: