Troubleshooting guide

MAGNUM VERSION 8 MANUAL REVISION 3.1
21
5. Authorization Function
The authorization code is a special four-character code that enables access to the Magnum controller.
The code may consist of any valid alpha/numeric characters if the system is being accessed through MCS-Connect,
however, the code must be numeric with values between 1 and 8 if it is to be entered through the Keypad/Display.
Each Magnum can have up to 10 different authorization codes, with four levels of authorization which provide differing
levels of functionality. The authorization code and the associated level cannot be viewed or changed through the
Keypad/Display or MCS-Connect, but only when the configuration file is opened in MCS-Config. The authorization
codes should be protected and remain confidential, or unauthorized personnel may gain access to the system and
perhaps cause irreparable damage.
Based upon the authorization level the following changes can be made through the Keypad/Display:
* Setpoints may have individual authorization levels; you must have the proper authorization to view or edit them.
**See the Setup screen of the configuration for authorization level(s) that are allowed unlimited resets per day.
Authorization levels below ‘Auth Level Bypass’ are allowed only a limited number of resets. Authorization levels at and
above ‘Auth Level Bypass’ are allowed unlimited lockout resets.
To get authorized through the Keypad/Display do the following:
1. Press ‘Menu’
2. Using , , , or keys, move cursor to ‘Passwords’
3. Press key.
4. Enter 4 digit password and press.
5. The authorization will be displayed.
6. Press ‘Menu’ to make next selection.
To get authorized through MCS-Connect do the following:
1. Highlight desired Magnum in the Site Information screen.
2. Click button.
3. Enter the 4 digit code into the pop-up box and click ok (or press the enter key).
4. Depending on the authorization level, the button will change to one of the following displays,
indicating if the code was accepted or not.
FUNCTION VIEW USER SERVICE SUPERVISOR FACTORY
Sensor offsets NO NO YES YES YES
Sensor diagnostics NO NO YES YES YES
Clear alarm history NO NO NO NO NO
Clear point information NO NO NO NO NO
Date and time set YES YES YES YES YES
Day of week set YES YES YES YES YES
Change No Flow Lockout or shut down NO NO NO NO YES
Change rotate Yes or No NO NO NO NO YES
Change Manual/Auto settings NO NO NO YES YES
Change Setpoint values * * * * YES
Change operating schedules NO NO YES YES YES
Change holiday dates NO NO YES YES YES
Lockout Reset ** ** ** ** YES
Change RS485 network settings NO NO NO YES YES
Change Ethernet network settings NO YES YES YES YES
Adjust Keypad/Display contrast YES YES YES YES YES
Transmit Software NO NO YES YES YES
Transmit/Receive Configuration NO NO YES YES YES