Enter the correct password to deactivate the Maximum Run Time function.
Select Yes to confirm you want to deactivate this function.
7.81. User Logic
Magnum provides the user the ability to customize control logic and calculated values. This is done in MCS-Config by
defining a Sensor Input, Relay Output, or Analog Output as a User Logic type. This type of point can be adjusted
through MCS-Connect by double clicking on the name of a User Logic point (This requires factory authorization) MCS-
Connect identifies a user-defined Relay Output by following the name with (UL), a Sensor Input’s Sensor Type cell has
User Logic as the type and Analog Output’s Type cell has Linear CTRL.
Operands
7.81.1.
Operands are the building blocks of the Magnum User Logic. An operand consists of two
parts: the top cell provides a drop down list to select the types and then a drop down list
to select the item within that type: